نویسندگان | Abbas Saberi noughabi,Kazem Mazlumi |
---|---|
نشریه | AUT Journal of Electrical Engineering |
شماره صفحات | 291-304 |
شماره سریال | 56 |
شماره مجلد | 2 |
نوع مقاله | Full Paper |
تاریخ انتشار | 2024 |
نوع نشریه | الکترونیکی |
کشور محل چاپ | ایران |
نمایه نشریه | isc |
چکیده مقاله
The operation of protection systems has a considerable impact on power system reliability. The main reason for cascading outages is protection system misoperation. Protection systems affect power system reliability from two perspectives: First, incorrect operation of the protection system due to the failure of any of its components that causes failure to operate or undesired tripping. Second is the incorrect operation of the protection system due to the incorrect setting of relays. In the second case, the protection system is healthy, and incorrect operation is only the result of the erroneous setting of relays. In this paper, an analysis of power system reliability regarding failure and incorrect settings of the protection system is paid. This paper proposes an eight-state Markov model for a transmission line and its protection system incorporating protection system miscoordination distingue from failure to operate and undesired trip. The situation of network lines in the period of simulation time has been determined by the sequential Monte Carlo method, and the reliability indices such as Loss of Load Probability (LOLP), Loss of Load Expectation (LOLE), Expected Energy Not Supplied (EENS), and Expected Frequency of Load Curtailment (EFLC) are calculated. The proposed model is applied to a 6-bus IEEE RBTS network, and the reliability indices are calculated and compared from both perspectives to show the importance of the proposed model.
tags: Power system reliability protection system failures Sequential Monte Carlo method Markov model of the protection system incorrect relay setting