| Authors | Reza Shariatinasab |
| Journal | Advanced Electromagnetics |
| Page number | 105-110 |
| Serial number | 9 |
| Volume number | 1 |
| Paper Type | Full Paper |
| Published At | 2020 |
| Journal Grade | ISI |
| Journal Type | Typographic |
| Journal Country | France |
| Journal Index | ISI،Scopus |
Abstract
In this paper, a methodology for determining the optimal
value of protection design parameters of transmission lines
(TLs) is presented. The proposed method calculates the
shielding failure flashover rate (SFFOR) and back flashover
rate (BFR) of transmission lines based on the Electrogeometric model of TLs and the Monte Carlo simulation
method, respectively. The accuracy of the proposed method
is verified by comparing the associated results with those
obtained with the IEEE FLASH program. The proposed
method can be used to achieve the minimum lightning
flashover rate (LFOR) of TLs by the minimum investment
cost. Indirectly, it can be used for determining the appropriate
value of the footing resistance, insulation strength, and
arrester rating to satisfy a specified number of LFOR that
might be given by the power utilities
Paper URL