A Methodology for Optimal Design of Transmission Lines Protection against Lightning Surges in the Presence of Arresters

نویسندگانReza Shariatinasab
نشریهAdvanced Electromagnetics
شماره صفحات105-110
شماره سریال9
شماره مجلد1
نوع مقالهFull Paper
تاریخ انتشار2020
رتبه نشریهISI
نوع نشریهچاپی
کشور محل چاپفرانسه
نمایه نشریهISI،Scopus

چکیده مقاله

In this paper, a methodology for determining the optimal value of protection design parameters of transmission lines (TLs) is presented. The proposed method calculates the shielding failure flashover rate (SFFOR) and back flashover rate (BFR) of transmission lines based on the Electrogeometric model of TLs and the Monte Carlo simulation method, respectively. The accuracy of the proposed method is verified by comparing the associated results with those obtained with the IEEE FLASH program. The proposed method can be used to achieve the minimum lightning flashover rate (LFOR) of TLs by the minimum investment cost. Indirectly, it can be used for determining the appropriate value of the footing resistance, insulation strength, and arrester rating to satisfy a specified number of LFOR that might be given by the power utilities

لینک ثابت مقاله

tags: Lightning performance, Transmission lines, Pollution