Analysis of Lightning-Related Stress in Transmission Lines Considering Ionization and Frequency-Dependent Properties of the Soil in Grounding Systems

نویسندگانReza Shariatinasab,Jinliang He
نشریهIEEE Transactions on Electromagnetic Compatibility
شماره صفحات2849-2857
شماره سریال62
شماره مجلد5
ضریب تاثیر (IF)1.658
نوع مقالهFull Paper
تاریخ انتشار2020
رتبه نشریهISI
نوع نشریهچاپی
کشور محل چاپایران
نمایه نشریهJCR،Scopus

چکیده مقاله

This article analyzes the performance of grounding systems buried in the ionized soil during the lightning discharge. To this aim, at first, a method to simultaneously analyze the transient response of grounding system considering the time-dependent nonlinear behavior arising from soil ionization and frequency dependence of soil electrical parameters related to the frequency content of the lightning surge is presented. The proposed method is performed by a combination of the harmonic balance method and the method of moment, which is aimed at representing an equivalent circuit to model the grounding system during the lightning discharge. The proposed model is validated by comparing the associated results with the published measurement and the numerical data for different grounding systems. Finally, an application of the proposed method is presented and the generated overvoltages across the insulator string caused by lightning strokes, the outage rates of transmission lines, and the lifetime of surge arresters are discussed

لینک ثابت مقاله

tags: Grounding electrodes, soil ionization, surge arresters (SAs), transient analysis.