چکیده مقاله
Accurate insulation risk assessment plays a critical role in ensuring the reliability of power transformers, given
the significant technical complexities involved in their design. Back flashover failure (BF) caused by lightning
overvoltages on incoming substation lines must be considered as an effective stress component in transformer
insulation design. These transient surges impose electrical stress on the paper-based insulation system of the
transformer. Since such insulation materials are non-self-restoring, the analysis of the voltage–time (V-T)
withstand characteristic is essential for insulation risk evaluation. These characteristics are typically derived
from laboratory tests on power transformers; however, insulation aging occurring during the testing process may
influence the accuracy of the extracted data. In real operating conditions, neglecting aging effects can lead to
inconsistencies in insulation coordination. This paper proposes a novel model for correcting aging- deviations in
voltage-time (V-T) characteristic curve, enabling a more accurate evaluation of insulation risk. Furthermore, the
proposed framework incorporates the cumulative impact of aging in order to estimate the overall insulation risk
of the transformer throughout its service life. The findings of this study contribute to safer and more optimized
design of power transformers and support improved insulation coordination under realistic operating conditions.